Download Print this page

Mitsubishi Electric FR-F800 Series Instruction Manual page 665

Hide thumbs Also See for FR-F800 Series:

Advertisement

 Appearance examples and outline dimensions
W
Noise filter model
HF3010C-SZA
HF3020C-SZA
HF3030C-SZA
HF3040C-SZA
HF3050C-SZA
HF3060C-SZA
HF3080C-SZA
HF3100C-SZA
HF3150C-SZA
HF3200C-SZA
HF3250C-SZA
HF3300C-SJB
HF3600C-SJB
HF31000C-SJB
HF31200C-SJB
HF31600C-SJB
(Unit: mm)
For details on this filter, contact Soshin Electric Co., Ltd.
9.3.3
Details of type certification for IP55 compatible
model
The inverters can be used in ships, except on the bridge and open deck areas.
 Details of certification
Certification body
NK (Nippon Kaiji Kyokai)
ABS (American Bureau of Shipping)
DNV GL (DNV GL AS)
 Precautions
The following are precautions for the system as a whole to be compliant with ship classification standards.
• To use the FR-F846-01160(55K)-C2 or lower, set AC voltage/frequency to three-phase 380 to 480 V, 50/60 Hz.
• Set the built-in EMC filter in the inverter to "enabled" (ON).
• Ensure that the finalized system which includes an inverter complies with the ship classification standards.
• For electromagnetic compatibility (EMC), install the recommended ferrite core (shown in the following page) or an
equivalent by two turns (passing the cable twice through the core) for wiring of control circuit terminals.
664
9. APPENDIX
9.3 Acquisition of type certification for ship classification standards (400 V class)
Downloaded from
ManualsNet.com
HF3000C-SZA(10A-30A)
W
220
270
310
395
400
340
390
480
Certificate number
14A020
19-YO1938937-PDA (Made in Japan)
19-YO1938937-PDA-DUP (Made in Japan)
TAE00000H2
search engine
W
D
66
80
100
110
120
190
190
200
Compatible from (Manufacture
year and month)
August 2019
December 2019
January 2020
HF3300C-SJB
HF3600C-SJB
H
78
84
210
230
260
140
160
190

Advertisement

loading