*1
The signal is OFF during power failure or undervoltage.
*2
This means the state during a fault occurrence or while the MRS signal is ON, etc.
*3
The signal is OFF while power is not supplied to the main circuit.
• To use the RY, RUN, or RUN3 signal, set the corresponding number selected from the following table in any parameter
from Pr.190 to Pr.196 (Output terminal function selection) to assign the function to an output terminal.
Output signal
RY
RUN
RUN3
NOTE
• The RUN signal (positive logic) is initially assigned to the terminal RUN.
 Fault (ALM) signal and Fault output 2 (ALM2) signal
• The fault signal (ALM or ALM2 signal) is output when an inverter protective function is activated.
• The ALM2 signal stays ON during the resetting the inverter after the Fault occurs.
• To use the ALM2 signal, set "94 (positive logic) or 194 (negative logic)" in any parameter from Pr.190 to Pr.196 (Output
terminal function selection) to assign the function to an output terminal.
• The ALM signal is initially assigned to the relay terminals A1, B1, and C1.
Inverter fault occurrence
(trip)
ON OFF
ALM
ON
ALM2
RES
Reset ON
NOTE
• For details on the inverter faults, refer to
 Input power shutoff like magnetic contactor (Y91 signal)
• The Fault output 3 (Y91) signal is output when a fault originating in the inverter circuit or a connection fault occurs.
• To use the Y91 signal, set "91 (positive logic) or 191 (negative logic)" in any parameter from Pr.190 to Pr.196 (Output
terminal function selection) to assign the function to an output terminal.
• The following is the list of faults that output the Y91 signal. (For details on faults, refer to
Inrush current limit circuit fault (E.IOH)
CPU fault (E.CPU)
CPU fault (E.6)
CPU fault (E.7)
Parameter storage device fault (control circuit board) (E.PE)
Parameter storage device fault (main circuit board) (E.PE2)
Internal storage device fault (E.PE6)
24 VDC power fault (E.P24)
Operation panel power supply short circuit/RS-485 terminals power supply short circuit
(E.CTE)
Output side earth (ground) fault overcurrent (E.GF)
Output phase loss (E.LF)
Internal circuit fault (E.BE)
Internal circuit fault (E.13/E.PBT)
336
5. PARAMETERS
5.8 (M) Item and output signal for monitoring
Downloaded from
ManualsNet.com
Pr.190 to Pr.196 settings
Positive logic
Negative logic
11
111
0
100
45
145
OFF
ON OFF
Reset processing
(about 1s)
Fault type
search engine
Time
page
594.
page
594.)