 Reverse action
When deviation X = (set point - measured value) is a plus value, the manipulated amount (output frequency) is increased, and
when the deviation is a minus value, the manipulated amount is decreased.
 Forward action
When deviation X = (set point - measured value) is a minus value, the manipulated amount (output frequency) is increased,
and when the deviation is a plus value, the manipulated amount is decreased.
Relationship between deviation and manipulated amount (output frequency)
PID action setting
Reverse action
Forward action
 Connection diagram
• Sink logic
• Pr.128 = 20
• Pr.183 = 14
• Pr.191 = 47
• Pr.192 = 16
• Pr.193 = 14
• Pr.194 = 15
*1
Prepare a power supply matched to the power supply specifications of the detector.
*2
The applied output terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
*3
The applied input terminals differ by the settings of Pr.178 to Pr.189 (Input terminal function selection)
*4
The AU signal need not be input.
Downloaded from
ManualsNet.com
[Heating]
+
X>0
Set
X<0
point
-
Feedback signal
(measured value)
[Cooling]
X>0
+
Set
X<0
point
-
Feedback signal
(measured value)
Deviation
Plus
Minus
Power supply
Forward
rotation
Reverse
rotation
PID control
selection
Setting
Potentiometer
(Set point setting)
AC1φ
200/220V 50/60Hz
search engine
Deviation
Cold
Increase
Hot
Decrease
Too cold
Decrease
Hot
Increase
Deviation
Inverter
MCCB
R/L1
S/L2
T/L3
STF
STR
RT(X14)
∗3
∗2
(PID)SU
SD
(FUP)FU
∗2
∗2
(FDN)OL
10
2
∗2
(RL)IPF
5
1
4
∗4
(Measured value) 4 to 20mA
0 24V
Power
∗1
supply
Set point
Measured value
Measured value
Set point
Pump
Motor
U
V
M
P
W
2-wire type
During PID action
Detector
Upper limit
Lower limit
-
+
Forward rotation
output
Reverse rotation
output
SE
Output signal common
5. PARAMETERS
5.11 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
3-wire
type
-
+
+
(OUT)
(24V)
(COM)