• ANALOG OUTPUT
Object Identifier
0
1
*1
R: Read only, W: Read/Write (Commandable values not supported), C: Read/Write (Commandable values supported)
Values written to the objects that support the commandable values are stored in the Priority Array, even when "Write Access Denied" is returned
due to inconsistency of the writing requirements such as the operating mode, on condition that the values are written within the setting range.
*2
Available regardless of the operation mode, operation command source, and speed command source.
• ANALOG VALUE
Object Identifier
1
Output frequency R
2
Output current
3
Output voltage
6
Running speed
Converter output
8
voltage
14
Output power
17
Load meter
Cumulative
20
energization time
Actual operation
23
time
Cumulative
25
power
52
PID set point
54
PID deviation
PID measured
67
value2
Second PID set
92
point
Second PID
94
deviation
Second PID
95
measured value
2
200
Alarm history 1
201
Alarm history 2
202
Alarm history 3
203
Alarm history 4
300
Speed scale
538
5. PARAMETERS
5.12 (N) Communication operation parameters
Downloaded from
ManualsNet.com
Present Value
Object Name
Access Type
Terminal FM (CA)
C
Terminal AM
C
Present Value
Object Name
Access Type
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
*2
C
search engine
*1
Controls actual output current level of terminal FM/CA.
Control is available when Pr.54 FM/CA terminal function
*2
selection = "85"
.
(Setting range: 0% to 200%)
Controls actual output voltage level of terminal AM.
Control is available when Pr.158 AM terminal function
*2
selection = "86"
.
(Setting range: -200% to 200%)
Description
*1
Represents the output frequency value.
Represents the output current value.
Represents the output voltage value.
Represents the running speed value.
Represents the converter output voltage value.
Represents the output power value.
Represents the load meter value.
Represents the cumulative energization time value.
Represents the actual operation time value.
Represents the cumulative power value.
Represents the PID set point.
Represents the PID deviation.
(Minus display is available with reference to 0%, in 0.1%
increment.)
Represents the PID measurement 2.
Represents the second PID set point.
Represents the second PID deviation.
(Minus display is available with reference to 0%, in 0.1%
increment.)
Represents the second PID measurement 2.
Represents the last fault record (fault record 1).
Represents the second most recent fault record (fault record 2).
Represents the third most recent fault record (fault record 3).
Represents the fourth most recent fault record (fault record 4).
Controls the ratio of the frequency command. (Setting range: 0.00
to 100.00) (Refer to
page
535.)
Description
Unit
percent
(98)
percent
(98)
Unit
hertz
(27)
amperes
(3)
volts
(5)
revolution-
per-minute
(104)
volts
(5)
kilowatts
(48)
percent
(98)
hours
(71)
hours
(71)
kilowatt-
hours
(19)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
percent
(98)