 Connection diagram
• The following diagram shows a connection example for emergency drive operation (in the commercial mode).
*1
Be careful of the capacity of the sequence output terminals.
The applied terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
Output terminal capacity
Open collector output of inverter
(RUN, SU, IPF, OL, FU)
Inverter relay output
(A1-C1, B1-C1, A2-B2, B2-C2)
Relay output option
(FR-A8AR)
*2
When connecting a DC power supply, insert a protective diode.
When connecting an AC power supply, use relay output terminals of the inverter or contact output terminals of the relay output option (FR-A8AR).
*3
The applied terminals differ by the settings of Pr.180 to Pr.189 (Input terminal function selection)
*4
The applied terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
NOTE
• Be sure to provide a mechanical interlock for MC2 and MC3.
 Emergency drive execution sequence
• When the X84 signal is ON for 3 seconds, the emergency drive is activated.
• The Y65 signal turns ON during emergency drive operation.
• "ED" appears on the operation panel during emergency drive operation.
• The ALM3 signal turns ON when a fault occurs during emergency drive operation.
• To activate the emergency drive, the X84 signal needs to be ON for three seconds while all the following conditions are
satisfied.
Item
Emergency drive parameter
settings
Contradictory condition
• When the "retry" (Pr.523 = "2[][], 3[][]") is selected, it is recommended to use the automatic restart after instantaneous
power failure function at the same time.
• Parameter setting is not available during emergency drive operation.
280
5. PARAMETERS
5.7 (H) Protective function parameter
Downloaded from
ManualsNet.com
MCCB
Emergency drive execution
Inverter/bypass
Reset
Output terminal permissible load
24 VDC 0.1 A
230 VAC 0.3 A
30 VDC 0.3 A
Pr.523 ≠ "9999"
Pr.524 ≠ "9999" (Setting is not required when Pr.523 = "100, 200, 300, or 400".)
None of the following conditions are satisfied.
• Enabling the electronic bypass sequence function
• During offline auto tuning
• Supplying power through terminals R1 and S1
• Pr.30 = "2 or 102"
search engine
MC2
MC3
R/L1
U
S/L2
V
T/L3
W

Y65
Emergency drive in operation


X84
Fault output during emergency drive
ALM3
CS
MC3

MC2
RES
MC2

SD
MC3
SE
Condition
M
MC2

MC3
24VDC