• The following shows the relationship between the input values of the analog input terminals and set point, measured value
and deviation. (Calibration parameter initial values)
Input terminal
Terminal 2
Terminal 1
Terminal 4
*6
Can be changed by Pr.73 Analog input selection, Pr.267 Terminal 4 input selection and the voltage/current input switch. (Refer to
NOTE
• Always calibrate the input after changing the voltage/current input specification with Pr.73 and Pr.267, and the voltage/current
input selection switch.
 Multistage set point input (Pr.1460 to Pr.1466)
• The set point can be selected by combining the ON/OFF status of the PDI1 to PDI3 signals. Up to eight set points can be
selected. Use Pr.1460 PID multistage set point 1 to Pr.1466 PID multistage set point 7 to set the target values for
selection.
• When "9999" is set in the selected multistage set point parameter, PID control is performed according to the Pr.128,
Pr.609, and Pr.133 settings.
Selected set point
Multistage set point 1
Multistage set point 2
Multistage set point 3
Multistage set point 4
Multistage set point 5
Multistage set point 6
Multistage set point 7
*1
When functions are not assigned to the input terminals, the signals are treated as OFF.
NOTE
• The multistage set point input is not available for the second PID.
• The priority of the set point input is as follows: Pr.1460 to Pr.1466> Pr.133> Pr.128.
426
5. PARAMETERS
5.11 (A) Application parameters
Downloaded from
ManualsNet.com
Input
*6
specification
Set point
0 V = 0%
0 to 5 V
5 V = 100%
0 V = 0%
0 to 10 V
10 V = 100%
0 mA = 0%
0 to 20 mA
20 mA = 100%
-5 to 0 V = 0%
0 to ±5 V
+5 V = +100%
-10 to 0 V = 0%
0 to ±10 V
+10 V = +100%
0 to 1 V = 0%
0 to 5 V
5 V = 100%
0 to 2 V = 0%
0 to 10 V
10 V = 100%
0 to 4 mA = 0%
0 to 20 mA
20 mA = 100%
*1
PDI1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
search engine
Relationship with analog input
Result
0 V = 0%
0 V = 0%
5 V = 100%
5 V = 100%
0 V = 0%
0 V = 0%
10 V = 100%
10 V = 100%
0 mA = 0%
0 mA = 0%
20 mA = 100%
20 mA = 100%
-5 V = -100%
-5 to 0 V = 0%
0 V = 0%
+5 V = +100%
+5 V = +100%
-10 V = -100%
-10 to 0 V = 0%
0 V = 0%
+10 V = +100%
+10 V = +100%
0 V = -20%
0 to 1 V = 0%
1 V = 0%
5 V = 100%
5 V = 100%
0 V = -20%
0 to 2 V = 0%
2 V = 0%
10 V = 100%
10 V = 100%
0 mA = -20%
0 to 4 mA = 0%
4 mA = 0%
20 mA = 100%
20 mA = 100%
*1
*1
PDI2
PDI3
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
Calibration parameter
Deviation
Pr.125, C2 to C4
When Pr.128 = "10": Pr.125,
C2 to C4.
When Pr.128 ≥ "1000": C12
to C15.
Pr.126, C5 to C7
Parameter for setting
As set in the Pr.128 and Pr.609 PID settings.
As set in Pr.133 when Pr.133 ≠ "9999".
Pr.1460
Pr.1461
Pr.1462
Pr.1463
Pr.1464
Pr.1465
Pr.1466
page
349.)