*4
The same operation is performed for the both settings.
NOTE
• Regardless of the Pr.71 (Pr.450) setting, offline auto tuning can be performed according to Pr.96 (Pr.463) Auto tuning
setting/status. (Refer to
 Using two types of motors (RT signal, Pr.450)
• When using two types of motors with one inverter, set Pr.450 Second applied motor.
• The setting value "9999" (initial value) disables the second motor.
• If Pr.450 ≠ 9999, the following parameters will be enabled by turning ON the Second function selection (RT) signal.
Electronic thermal O/L relay
Applied motor
Motor capacity
Number of motor poles
Motor excitation current
Rated motor voltage
Rated motor frequency
Motor constant (R1)
Motor constant (R2)
Motor constant (L1)/d-axis inductance (Ld)
Motor constant (L2)/q-axis inductance (Lq)
Motor constant (X)
Auto tuning setting/status
Frequency search gain
Online auto tuning selection
Induced voltage constant (phi f)
Motor Ld decay ratio
Motor Lq decay ratio
Starting resistance tuning compensation
Starting magnetic pole position detection pulse
width
Maximum motor frequency
Motor inertia (integer)
Motor inertia (exponent)
Motor protection current level
Torque current/Rated PM motor current
NOTE
• The RT signal is the Second function selection signal. The RT signal also enables other second functions. (Refer to
• The RT signal is assigned to terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
 Automatic change of torque boost for the SF-PR motor
• When the SF-PR motor is selected (Pr.71 = "70, 73, or 74"), the Pr.0 Torque boost is automatically changed to enable
output of the 6 Hz 150% torque under V/F control by setting Pr.81 Number of motor poles according to the number of
the SF-PR motor poles.
NOTE
• When selecting the automatic change of torque boost for the SF-PR motor, set Pr.14 Load pattern selection = "0".
• When the Pr.0 setting is changed from its initial value, the automatic change is not performed.
Downloaded from
ManualsNet.com
page 383
for offline auto tuning.)
Function
Pr.51
Pr.450
Pr.453
Pr.454
Pr.455
Pr.456
Pr.457
Pr.458
Pr.459
Pr.460
Pr.461
Pr.462
Pr.463
Pr.560
Pr.574
Pr.738
Pr.739
Pr.740
Pr.741
Pr.742
Pr.743
Pr.744
Pr.745
Pr.746
Pr.860
search engine
RT signal ON (second motor)
RT signal OFF (first motor)
Pr.9
Pr.71
Pr.80
Pr.81
Pr.82
Pr.83
Pr.84
Pr.90
Pr.91
Pr.92
Pr.93
Pr.94
Pr.96
Pr.298
Pr.95
Pr.706
Pr.711
Pr.712
Pr.717
Pr.721
Pr.702
Pr.707
Pr.724
Pr.725
Pr.859
5. PARAMETERS
5.10 (C) Motor constant parameters
1
2
3
4
5
6
7
8
9
10
page
377.)
381

Advertisement

loading