Mitsubishi Electric FR-F800 Series Instruction Manual page 288

Hide thumbs Also See for FR-F800 Series:

Advertisement

5.7.9
When E.PE6 (Internal storage device fault) occurs, faulty area in the internal storage device can be checked by reading Pr.890.
When the read value of Pr.890 is "7" or smaller, an inverter reset after All parameter clear can return the operation to normal.
(The parameters that had been changed before All parameter clear must be set again.)
Pr.
890
H325
• Pr.890 read
• Use the read value of Pr.890 to check the faulty area.
The following table shows faulty areas indicated by the read value of Pr.890. Some read values indicate that there are
multiple faulty areas. (For example, the read value "7" indicates that all the areas described in No. 1 to No. 3 are faulty.)
No.
1
1, 3, 5, 7
2
2, 3, 6, 7
3
4, 5, 6, 7
4
8 to 9999
5.7.10 Limiting the output frequency (maximum/minimum
Motor speed can be limited. Clamp the upper and lower limits of the output frequency.
Pr.
1
Maximum frequency
H400
2
Minimum frequency
H401
18
High speed maximum
H402
frequency
*1
For the FR-F820-02330(55K) or lower, and FR-F840-01160(55K) or lower.
*2
For the FR-F820-03160(75K) or higher, and FR-F840-01800(75K) or higher.
 Setting the maximum frequency (Pr.1, Pr.18)
• Set Pr.1 Maximum frequency to the upper limit of the output frequency. If the value of the frequency command given is
higher than the setting, the output frequency is clamped at the maximum frequency.
• To operate at a frequency higher than the 120 Hz, adjust the upper output frequency limit with Pr.18 High speed
maximum frequency. (When setting a frequency in Pr.18, the Pr.1 setting automatically changes to the frequency set in
Pr.18. Also, when setting a frequency in Pr.1, the Pr.18 setting automatically changes to the frequency set in Pr.1.)
Output frequency
(Hz)
Pr.1
Pr.18
Pr.2
(4mA)
Clamped at the
minimum frequency
Downloaded from
ManualsNet.com
Checking faulty area in the internal storage device
Name
Internal storage device status
indication
• Pr.890 setting read
Read value
Storage area other than the area for parameter settings is faulty (such as area for the set frequency). (When
All parameter clear is performed, the set frequency, remotely-set frequency, host name for Ethernet
communication, and offline auto tuning data are cleared.)
Storage area for standard parameter settings is faulty.
Storage area for communication parameter settings is faulty.
Area for manufacturer setting
frequency)
Name
Initial value
120 Hz
60 Hz
0 Hz
120 Hz
60 Hz
Clamped at the
maximum frequency
Frequency setting
0
5, 10V
(20mA)
search engine
Initial value
Setting range
0
(0 to 9999)
Description
Setting range
*1
0 to 120 Hz
*2
0 to 120 Hz
*1
0 to 590 Hz
*2
Description
A detected faulty area can be indicated in the
internal storage device.
Description
Set the upper limit of the output frequency.
Set the lower limit of the output frequency.
Set when operating at 120 Hz or higher.
5.7 (H) Protective function parameter
1
2
3
4
5
6
7
8
9
10
287
5. PARAMETERS