 Sink logic and source logic
• In the sink logic, a signal turns ON when a current exits from the corresponding signal input terminal.
Terminal SD is common to the contact input signals. Terminal SE is common to the open collector output signals.
• In the source logic, a signal turns ON when a current enters into the corresponding signal input terminal.
Terminal PC is common to the contact input signals. Terminal SE is common to the open collector output signals.
Current flow concerning the input/output signal
when sink logic is selected
Current
• When using an external power supply for transistor output
Sink logic
Use terminal PC as a common terminal, and perform wiring as
shown below. (Do not connect terminal SD on the inverter with
the terminal of 0 V for the external power supply. When using
terminals PC-SD as a 24 VDC power supply, do not install an
external power supply in parallel with the inverter. Doing so
may cause a malfunction in the inverter due to undesirable
currents.)
QY40P type transistor
output unit
Constant
voltage
circuit
Downloaded from
ManualsNet.com
Sink logic
STF
R
STR
R
SD
Inverter
DC input (sink type)
<Example: QX40>
RUN
TB1
R
-
+
TB17
SE
24 VDC
Current flow
Inverter
TB1
STF
TB2
STR
TB17
PC
TB18
24 VDC SD
Current flow
search engine
Current flow concerning the input/output signal
when source logic is selected
Source logic
Sink
Current
connector
Inverter
R
Source logic
Use terminal SD as a common terminal, and perform wiring as
shown below. (Do not connect terminal PC on the inverter with
the terminal of +24 V for the external power supply. When
using terminals PC-SD as a 24 VDC power supply, do not
install an external power supply in parallel with the inverter.
Doing so may cause a malfunction in the inverter due to
undesirable currents.)
QY80 type transistor
output unit
24 VDC
(SD)
Constant
voltage
circuit
PC
STF
R
STR
R
DC input (source type)
<Example: QX80>
RUN
TB1
R
R
TB18
+
-
SE
24 VDC
Current flow
Inverter
PC
TB1
STF
TB2
STR
TB17
Fuse
TB18
SD
Current flow
2. INSTALLATION AND WIRING
2.6 Control circuit
1
2
3
4
Source
connector
5
6
7
8
9
10
24 VDC
(SD)
65