NOTE
• For details on connecting the brake unit, high power factor converter (FR-HC2), multifunction regeneration converter (FR-XC),
or power regeneration common converter (FR-CV), refer to
of each option.
• Setting Pr.30 = "2" will reset the inverter, and "Err" is displayed on the operation panel during the reset.
 Logic reversing of the Inverter run enable signal (X10 signal, Pr.599)
• Use Pr.599 X10 terminal input selection to select the X10 signal input specification between normally open (NO contact)
and normally closed (NC contact). With the normally closed (NC contact) input specification, the inverter output is shut off
by turning OFF (opening) the X10 signal.
• Changing the inverter logic (NO/NC contact) with the Pr.599 setting is required according to the logic of the Inverter run
enable signal sent from the option unit.
• The response time of the X10 signal is within 2 ms.
Output frequency
X10 signal (Pr.599=0)
X10 signal (Pr.599=1)
• Relationship between Pr.599 and the Inverter run enable signal of each option unit
Pr.599 setting
0 (initial value of standard models
and IP55 compatible models)
1
(initial value of separated converter
types)
NOTE
• If the X10 signal is unassigned while Pr.30 = "2 or 102" (FR-HC2/FR-XC/FR-CV connection) or "10, 11, 110, or 111" (DC
feeding mode 1), the MRS signal can be used as the X10 signal. At this time, logic setting for the signal will follow Pr.17 MRS
input selection.
• The X10 signal is valid when Pr.30 = "2, 10, 11, 102, 110, or 111".
• The MRS signal is valid from either of communication or external, but when the MRS signal is to be used as the Inverter run
enable (X10) signal, it must be input from external.
• When the FR-HC or MT-HC is connected, set Pr.599 = "0 (initial value)".
• When the terminal assignment is changed with Pr.178 to Pr.189 (Input terminal function selection), wiring may be mistaken
due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming the function
of each terminal.
568
5. PARAMETERS
5.13 (G) Control parameters
Downloaded from
ManualsNet.com
Motor coasts to stop
Time
ON
OFF
Corresponding signals of the option unit
FR-HC2
RDY (negative
logic) (initial
RYB
setting)
RDY (positive
RYA
logic)
search engine
page
80. For details of each option, refer to the Instruction Manual
FR-XC
FR-CV
FR-CC2
RDYB
RDB
RDYA
RDA
Operation according to the X10
signal status
X10-ON: Inverter output shutoff (NO
contact)
X10-OFF: Inverter output shutoff (NC
contact)