 Setting multiple PID functions
• When the second PID function is set, two sets of PID functions can be switched for use. The PID setting is selected as
shown in the following table.
Pr.128 setting
(First PID setting)
"0" or not applied to the
frequency
"0" or not applied to the
frequency
Applied to the frequency
Applied to the frequency
*1
While Pr.155 = "0", the second function is enabled immediately after the RT signal turns ON. While Pr.155 = "10", the second function is enabled
only during constant speed operation when the RT signal turns ON. (For the details, refer to
• The parameters and signals for the second PID function are in the same way as the following parameters and signals of
the first PID function. Refer to the first PID function when setting the second PID functions.
Classification
Parameter
Classification
Input signal
Output signal
Downloaded from
ManualsNet.com
Pr.753 setting
(Second PID setting)
"0" or not applied to the
frequency
Applied to the frequency
"0" or not applied to the
frequency
Applied to the frequency
First PID function parameters
Pr.
PID control automatic switchover
127
frequency
128
PID action selection
129
PID proportional band
130
PID integral time
131
PID upper limit
132
PID lower limit
133
PID action set point
134
PID differential time
553
PID deviation limit
554
PID signal operation selection
Output interruption detection
575
time
Output interruption detection
576
level
577
Output interruption cancel level
PID set point/deviation input
609
selection
PID measured value input
610
selection
First PID function parameters
Signal
X14
PID control valid
PID forward/reverse action
X64
switchover
X72
PID P control switchover
FUP
PID upper limit
FDN
PID lower limit
PID forward/reverse rotation
RL
output
PID
During PID control activated
SLEEP
PID output interruption
Y48
PID deviation limit
search engine
Pr.155
RT signal
*1
setting
OFF
0
ON
10
Name
Pr.
754
753
756
757
1143
1144
755
758
1145
1146
1147
1148
1149
1140
1141
Name
Signal
X80
X79
X73
FUP2
FDN2
RL2
PID2
SLEEP2
Y205
PID setting applied to the output
frequency
Control other than PID control
Second PID setting
First PID setting
First PID setting
Second PID setting
First PID setting
page
377.)
Second PID function parameters
Name
Second PID control automatic
switchover frequency
Second PID action selection
Second PID proportional band
Second PID integral time
Second PID upper limit
Second PID lower limit
Second PID action set point
Second PID differential time
Second PID deviation limit
Second PID signal operation selection
Second output interruption detection
time
Second output interruption detection
level
Second output interruption cancel level
Second PID set point/deviation input
selection
Second PID measured value input
selection
Second PID function parameters
Name
Second PID control valid
Second PID forward/reverse action
switchover
Second PID P control switchover
Second PID upper limit
Second PID lower limit
Second PID forward/reverse rotation
output
During second PID control activated
During second PID output shutoff
Second PID deviation limit
5. PARAMETERS
5.11 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
435

Advertisement

loading