• Calibration parameter according to the terminal 4 function
Pr.858
Terminal function
setting
0 (initial
Frequency command
value)
Stall prevention operation
4
*1
level
9999
No function
*1
Use Pr.148 Stall prevention level at 0 V input and Pr.149 Stall prevention level at 10 V input to adjust bias and gain for setting the stall
prevention operation level under V/F control and Advanced magnetic flux vector control.
Changing the frequency for the maximum analog input (Pr.125, Pr.126)
• Use Pr.125 (Pr.126) to change the frequency setting (gain) for the maximum analog input voltage (current).
(C2 (Pr.902) to C7 (Pr.905) settings do not need to be changed.)
Analog input bias/gain calibration (C2 (Pr.902) to C7 (Pr.905), C12 (Pr.917)
to C15 (Pr.918))
• The "bias" and "gain" functions serve to adjust the relationship between a setting input signal and the output frequency. A
setting input signal is such as a 0 to 5 VDC, 0 to 10 VDC, or 4 to 20 mADC signal externally input to set the output
frequency.
• Set the bias frequency of the terminal 2 input using C2 (Pr.902). (It is initially set to the frequency at 0 V.)
• Use Pr.125 to set the output frequency to the frequency command voltage (current) set by Pr.73 Analog input selection.
• Set the bias frequency of the terminal 1 input using C12 (Pr.917). (It is initially set to the frequency at 0 V.)
• Set the gain frequency of the terminal 1 input using C14 (Pr.918). (It is initially set to the frequency at 10 V.)
• Set the bias frequency of the terminal 4 input using C5 (Pr.904). (It is initially set to the frequency at 4 mA.)
• Use Pr.126 to set the output frequency to the 20 mA input of the frequency command current (4 to 20 mA).
60Hz
(50Hz)
Bias
C2(Pr.902)
C12(Pr.917)
0
0
0
0
C3(Pr.902)
C13(Pr.917)
• There are three methods to adjust the bias/gain frequency setting voltage (current).
Adjustment by applying voltage (current) between terminals 2 and 5 (4 and 5) to set the voltage (current) at the bias/gain
page 360
frequency.
Adjustment by selecting the voltage (current) at the bias/gain frequency without applying voltage (current) between
terminals 2 and 5 (4 and 5).
Adjustment by changing the frequency without adjusting the voltage (current).
358
5. PARAMETERS
5.9 (T) Multi-function input terminal parameters
Downloaded from
ManualsNet.com
C5 (Pr.904) Terminal 4 frequency setting
bias frequency
C6 (Pr.904) Terminal 4 frequency setting
bias
C38 (Pr.932) Terminal 4 bias command
(torque)
C39 (Pr.932) Terminal 4 bias (torque)
—
Initial value
100%
5V
Frequency setting signal
10V
20mA
C4(Pr.903)
C15(Pr.918)
page 361
search engine
Calibration parameter
Bias setting
60Hz
(50Hz)
Output frequency
(Hz)
Gain
Pr.125
C14(Pr.918)
Bias
C5
(Pr.904)
0
0
0
0
C6(Pr.904)
Gain setting
Pr.126 Terminal 4 frequency setting gain
frequency
C7 (Pr.905) Terminal 4 frequency setting gain
C40 (Pr.933) Terminal 4 gain command
(torque)
C41 (Pr.933) Terminal 4 gain (torque)
—
Initial value
20
100%
4
20mA
Frequency setting signal
1
5V
2
10V
C7(Pr.905)
page 362
Gain
Pr.126