4.4
Frequently-used parameters (simple mode
parameters)
Parameters that are frequently used for the FR-F800 series are grouped as simple mode parameters.
When Pr.160 User group read selection = "9999", only the simple mode parameters are displayed on the operation panel.
This section explains the simple mode parameters.
4.4.1
Simple mode parameter list
For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter's setting, change and check can be made
on the operation panel (FR-DU08).
• Pr.160 User group read selection can narrow down the displayed parameters to only the simple mode parameters. Set
Pr.160 User group read selection as required. (To change the parameter setting, refer to
Pr.160 setting
9999 (FM type initial value)
0 (CA type initial value)
1
Pr.
Pr. group
0
G000
1
H400
2
H401
3
G001
4
D301
5
D302
6
D303
7
F010
8
F011
H000
9
C103
79
D000
120
4. BASIC OPERATION

4.4 Frequently-used parameters (simple mode parameters)

Downloaded from
ManualsNet.com
Only simple mode parameters are displayed.
All parameters (simple mode parameters and extended parameters) are displayed.
Only parameters registered in user groups are displayed.
Name
Increment
6%
4%
3%
Torque boost
0.1%
2%
1.5%
1%
120 Hz
Maximum
0.01 Hz
frequency
60Hz
Minimum
0.01 Hz
0 Hz
frequency
Base frequency 0.01 Hz
60 Hz
Multi-speed
setting (high
0.01 Hz
60 Hz
speed)
Multi-speed
setting (middle
0.01 Hz
30 Hz
speed)
Multi-speed
setting (low
0.01 Hz
10 Hz
speed)
5 s
Acceleration
0.1 s
time
15 s
10 s
Deceleration
0.1 s
time
30s
Electronic
*7
0.01 A
Inverter rated
thermal O/L
current
*8
0.1A
relay
Operation mode
1
0
selection
search engine
Description
*11
Initial value
Range
FM
CA
*1
*2
*3
0% to 30%
*4
*5
*6
*7
0 to 120Hz
*8
0 to 120 Hz
50 Hz
0 to 590 Hz
50 Hz
0 to 590 Hz
0 to 590 Hz
0 to 590 Hz
*9
0 to 3600 s
*10
*9
0 to 3600 s
*10
*7
0 to 500 A
*8
0 to 3600A
0 to 4, 6, 7
page
116.)
Application
Set this parameter to obtain a higher starting
torque under V/F control. Also set this when a
loaded motor cannot be driven, the warning
"OL" occurs, and the inverter output is shut off
with the fault indication "E.OC1".
Set the upper limit for the output frequency.
Set the lower limit for the output frequency.
Set this parameter when the rated motor
frequency is 50 Hz. Check the rating plate of
the motor.
Pre-set the speeds that will be switched
among by terminals.
Set the acceleration time.
Set the deceleration time.
Protects the motor from heat.
Set the rated motor current.
Select the start and frequency command
sources.
Refer
to
page
551
287
552
125,
130,
263
228
266
240