5.4.16 Setting multiple parameters by batch
The setting of particular parameters is changed by batch, such as communication parameters for connection with the Mitsubishi
Electric human machine interface (GOT), the parameters for the rated frequency (50/60 Hz) setting, or the parameters for
acceleration/deceleration time increment.
Multiple parameters are changed automatically. Users do not have to consider each parameter number (automatic parameter
setting).
Pr.
999
Automatic parameter
E431
setting
*1
The read value is always "9999".
 Automatic parameter setting (Pr.999)
• Select which parameters to automatically set from the following table, and set them in Pr.999. Multiple parameter settings
are changed automatically. Refer to
Pr.999
setting
1
Sets the standard monitor indicator setting of PID control.
2
Automatically sets the monitor indicator for PID control.
Automatically sets the communication parameters for the GOT
10
connection with PU connector ("Controller Type" in GOT:
FREQROL 500/700/800, SENSORLESS SERVO)
Automatically sets the communication parameters for the GOT
11
connection with RS-485 terminals ("Controller Type" in GOT:
FREQROL 500/700/800, SENSORLESS SERVO)
Automatically sets the communication parameters for the GOT
12
connection with a PU connector ("Controller Type" in GOT:
FREQROL 800 (Automatic Negotiation))
Automatically sets the communication parameters for the GOT
13
connection with RS-485 terminals ("Controller Type" in GOT:
FREQROL 800 (Automatic Negotiation))
50 Hz rated
20
frequency
60 Hz rated
21
frequency
NOTE
• If the automatic setting is performed with Pr.999 or the automatic parameter setting mode, the settings including the changed
parameter settings (changed from the initial setting) will be automatically changed. Before performing the automatic setting,
confirm that changing the parameters will not cause any problem.
Downloaded from
ManualsNet.com
Name
Initial value
*1
9999
page 212
Description
Sets the related parameters of the rated
frequency according to the power supply
frequency
search engine
Setting
range
1
Standard PID display setting
2
Extended PID display setting
10
GOT initial setting (PU connector)
11
GOT initial setting (RS-485 terminal)
12
GOT initial setting (PU connector)
13
GOT initial setting (RS-485 terminal)
20
50 Hz rated frequency
21
60 Hz rated frequency
9999
No action
for the list of parameters that are changed automatically.
Operation in the automatic parameter setting mode
"
"1".
"
"2".
"
"1".
"
"2".
"
"1".
Description
"Controller Type" in GOT:
FREQROL 500/700/800,
SENSORLESS SERVO
"Controller Type" in GOT:
FREQROL 800 (Automatic
Negotiation)
" (AUTO) → "
" (PID) → Write
" (AUTO) → "
" (PID) → Write
" (AUTO) → "
" (GOT) → Write
" (AUTO) → "
" (GOT) → Write
" (AUTO) → "
" (F50) → Write
5. PARAMETERS
5.4 (E) Environment setting parameters
1
2
3
4
5
6
7
8
9
10
211