Download Print this page

Mitsubishi Electric FR-F800 Series Instruction Manual page 345

Hide thumbs Also See for FR-F800 Series:

Advertisement

• Terminal CA output [mA] = 20 [mA] × (Analog remote output value - 1000)/100
Where the output range is 0 to 20 mA.
Output current [mA]
800
• When Pr.158 AM terminal function selection = "87, 88, 89, or 90", an analog voltage can be output via terminal AM.
• Terminal AM output [V] = 10 [V] × (Analog remote output value - 1000)/100
The output range is -10 to +10 V regardless of the Pr.290 Monitor negative output selection setting.
Output voltage [V]
800
900
 Analog remote output data retention (Pr.655)
• When the power supply is reset (including a power failure) while Pr.655 Analog remote output selection = "0" (initial
value) or 10" and, the remote analog output (Pr.656 to Pr.659) returns to its initial value (1000%).
• When Pr.655 = "1 or 11", the remote output data is stored in EEPROM before the inverter power is turned OFF. This means
that the signal output setting after power restoration is the same as that before the power was turned OFF. However, when
Pr.655 = "1", the data during an inverter reset (terminal reset or reset request via communication) is not saved.
• When Pr.655 = "10 or 11", the remote output data in the signal before the reset is stored even during an inverter reset.
• When the setting in Pr.655 is changed, the remote analog output (Pr.656 to Pr.659) returns to its initial value (1000%).
ON/OFF example for positive logic
Pr.655 = 0, 10
Power
OFF
supply
Analog
output
Analog output
Signal condition during a reset
Pr.655 = 0, 1
ON
Reset
Analog
output
∗ When Pr.655 = "1", the signal condition saved in EEPROM
(condition of the last power OFF) is applied.
344
5. PARAMETERS
5.8 (M) Item and output signal for monitoring
Downloaded from
ManualsNet.com
20
0
1000
1100
Analog remote output value [%]
Terminal CA
10
0
1000
1100
Analog remote output value [%]
-10
Terminal AM
Pr.655 = 1, 11
Power
OFF
supply
Analog
output
Analog
clear
output
saved
Pr.655 = 10, 11
ON
Reset
Analog
output
search engine
1200
1200
Inverter
reset time
(about 1s)
Analog
output
held

Advertisement

loading