4.7 Basic iQpump Setup and Application Preset Parameters

4.7
Basic iQpump Setup and Application Preset Parameters
This section explains the basic settings required for initial drive operation. Checking these basic parameter settings will help
to ensure a successful drive start-up.
information is required for parameters not listed in this section.
n
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
No.
A1-01
Setting 0: Operation only
Access to only parameters A1-01, A1-04, and all U monitor parameters.
Setting 1: User Parameters
Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the
Setup Mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
All parameters can be viewed and edited.
Setting 3: Lock Parameters
Parameters that are normally visible in the advanced access level (A1-01 = 2) are still visible, but the only parameters that can
be changed are A1-01 and A1-04.
The Auto Tuning and Pump Quick Setup menus will not be displayed.
Figure 4.29 Help Message Example (Optional HOA Keypad, JVOP-183, Home Screen)
Notes on Parameter Access
• If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all A2
parameters cannot be modified.
• If a digital input terminal programmed for "Program lockout" (H1-oo = 1B) is enabled, parameter values cannot be
modified, even if A1-01 is set to 1 or 2.
• If parameters are changed via serial communication, it will not be possible to edit or change parameter settings with the
digital operator until an Enter command is issued to the drive from the serial communication.
n
A1-03: Initialize Parameters
Resets parameters to default values or performs an Application Preset for fan or pump applications. After initialization, the
setting for A1-03 automatically returns to 0.
210
Refer to Parameter List on page 349
Parameter Name
Access Level Selection
for a complete listing of drive parameters if more
Setting Range
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Default
0 to 3
2