Determining Wire And Fuse Sizes - Hitachi WJ200 Series Instruction Manual

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

2−16

Determining Wire and Fuse Sizes

The maximum motor currents in your application determines the recommended wore
size. The following table gives the wire size in AWG. The "Power Lines" column applies
to the inverter input power, output wires to the motor, the earth ground connection,
and any other components shown in the "Basic System Description" on page 2-4. The
"Signal Lines" column applies to any wire connecting to the two green connectors just
inside the front cover panel.
Motor Output
kW
HP
VT
CT
VT
0.2
0.1
¼
0.4
0.2
½
0.55
0.4
¾
1.1
0.75
1.5
2.2
1.5
3
3.0
2.2
4
0.2
0.1
¼
0.4
0.2
½
0.75
0.4
1
1.1
0.75
1.5
2.2
1.5
3
3.0
2.2
4
5.5
3.7
7.5
7.5
5.5
10
11
7.5
15
15
11
20
18.5
15
25
0.75
0.4
1
1.5
0.75
2
2.2
1.5
3
3.0
2.2
4
4.0
3.0
5
5.5
4.0
7.5
7.5
5.5
10
11
7.5
15
15
11
20
18.5
15
25
Note 1: Field wiring must be made by a UL-Listed and CSA-certified closed-loop
terminal connector sized for the wire gauge involved. Connector must be fixed
by using the crimping tool specified by the connector manufacturer.
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66ft. (20m).
Note 4: Use 18 AWG / 0.75mm
terminals).
Inverter Model
CT
1/8
WJ200-001SF
¼
WJ200-002SF
½
WJ200-004SF
WJ200-007SF
1
2
WJ200-015SF
WJ200-022SF
3
1/8
WJ200-001LF
¼
WJ200-002LF
½
WJ200-004LF
1
WJ200-007LF
WJ200-015LF
2
3
WJ200-022LF
WJ200-037LF
5
WJ200-055LF
7.5
10
WJ200-075LF
15
WJ200-110LF
WJ200-150LF
20
WJ200-004HF
½
WJ200-007HF
1
WJ200-015HF
2
WJ200-022HF
3
WJ200-030HF
4
WJ200-040HF
5
7.5
WJ200-055HF
WJ200-075HF
10
WJ200-110HF
15
WJ200-150HF
20
wire for the alarm signal wire ([AL0], [AL1], [AL2]
2
Wiring
Signal
Power Lines
Lines
2
AWG16 / 1.3mm
(75°C only)
2
AWG12 / 3.3mm
(75°C only)
2
AWG10 / 5.3mm
2
AWG16 / 1.3mm
2
AWG14 / 2.1mm
(75°C only)
2
AWG12 / 3.3mm
(75°C only)
2
AWG10 / 5.3mm
(75°C only)
18 to 28
AWG / 0.14
2
AWG6 / 13mm
to 0.75 mm
(75°C only)
shielded wire
2
AWG4 / 21mm
(see Note 4)
(75°C only)
2
AWG2 / 34mm
(75°C only)
2
AWG16 / 1.3mm
2
AWG14 / 2.1mm
2
AWG12 / 3.3mm
(75°C only)
2
AWG10 / 5.3mm
(75°C only)
2
AWG6 / 13mm
(75°C only)
2
AWG6 / 13mm
(75°C only)
Applicable
equipment
Fuse (UL-rated,
class J, 600V)
10A
15A
30A
10A
15A
20A
30A
2
40A
80A
80A
10A
15A
20A
40A
40A

Advertisement

Table of Contents
loading