Input Function Summary Table – This table shows all thirty-one intelligent input
functions at a glance. Detailed description of these functions, related parameters and
settings, and example wiring diagrams are in "Using Intelligent Input Terminals" on
page 4-8.
Option
Terminal
Code
Symbol
00
FW
FORWARD Run/Stop
01
RV
Reverse Run/Stop
Multi-speed Select,
02
CF1 *1
Bit 0 (LSB)
Multi-speed Select,
03
CF2
Bit 1
Multi-speed Select,
04
CF3
Bit 2
Multi-speed Select,
05
CF4
Bit 3 (MSB)
06
JG
Jogging
07
DB
External DC braking
Set (select) 2nd Motor
08
SET
Data
2-stage Acceleration
09
2CH
and Deceleration
11
FRS
Free-run Stop
12
EXT
External Trip
Unattended Start
13
USP
Protection
Commercial
14
CS
source switchover
15
SFT
Software Lock
Analog Input
16
AT
Voltage/Current Select
18
RS
Reset Inverter
PTC thermistor Thermal
19
PTC
Protection
(C005 only)

Input Function Summary Table

Function Name
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
power
OFF
ON
OFF
ON
OFF
ON
OFF
ANLG
OPEN
Description
Inverter is in Run Mode, motor runs forward
Inverter is in Stop Mode, motor stops
Inverter is in Run Mode, motor runs reverse
Inverter is in Stop Mode, motor stops
Binary encoded speed select, Bit 0, logical 1
Binary encoded speed select, Bit 0, logical 0
Binary encoded speed select, Bit 1, logical 1
Binary encoded speed select, Bit 1, logical 0
Binary encoded speed select, Bit 2, logical 1
Binary encoded speed select, Bit 2, logical 0
Binary encoded speed select, Bit 3, logical 1
Binary encoded speed select, Bit 3, logical 0
Inverter is in Run Mode, output to motor runs at jog
parameter frequency
Inverter is in Stop Mode
DC braking will be applied during deceleration
DC braking will not be applied
The inverter uses 2nd motor parameters for
generating frequency output to motor
The inverter uses 1st (main) motor parameters for
generating frequency output to motor
Frequency output uses 2nd-stage acceleration and
deceleration values
Frequency output uses standard acceleration and
deceleration values
Causes output to turn OFF, allowing motor to free
run (coast) to stop
Output
operates
normally,
deceleration stop motor
When assigned input transitions OFF to ON,
inverter latches trip event and displays
No trip event for ON to OFF, any recorded trip
events remain in history until reset
On powerup, the inverter will not resume a Run
command (mostly used in the US)
On powerup, the inverter will resume a Run
command that was active before power loss
Motor can be driven by commercial power
Motor is driven via the inverter
The keypad and remote programming devices are
prevented from changing parameters
The parameters may be edited and stored
Refer to "Analog Input Settings" on page 3-13.
The trip condition is reset, the motor output is
turned OFF, and powerup reset is asserted
Normal power-ON operation
When a thermistor is connected to terminal [5] and
[L], the inverter checks for over-temperature and
will cause trip event and turn OFF output to motor
A disconnect of the thermistor causes a trip event,
and the inverter turns OFF the motor