Hitachi WJ200 Series Instruction Manual page 133

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

3−52
Func.
Code
Overload restriction
B021
operation mode
Overload restriction
B221
operation mode, 2
Overload restriction level
B022
Overload restriction level,
B222
2
motor
nd
Deceleration rate at
B023
overload restriction
Deceleration rate at
B223
overload restriction, 2
motor
Overload restriction
b024
operation mode 2
Overload restriction level 2
b025
Deceleration rate 2 at
b026
overload restriction
OC suppression selection *
b027
"b" Function
Name
Select the operation mode during
overload conditions, four options,
option codes:
00...Disabled
01...Enabled for acceleration and
02...Enabled for constant speed
only
03...Enabled for acceleration and
constant speed, increase speed
at regen.
nd
motor
Sets the level of overload
restriction, between 20% and 200%
of the rated current of the inverter,
setting resolution is 1% of rated
current
Sets the deceleration rate when
inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
nd
Select the operation mode during
overload conditions, four options,
option codes:
00...Disabled
01...Enabled for acceleration and
02...Enabled for constant speed
only
03...Enabled for acceleration and
constant speed, increase speed
at regen.
Sets the level of overload
restriction, between 20% and 200%
of the rated current of the inverter,
setting resolution is 1% of rated
current
Sets the deceleration rate when
inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
Two option codes:
00...Disabled
01...Enabled
Description
constant speed
constant speed
Defaults
Run
Mode
Lnitial data
Units
Edit
01
01
Rated
Amps
current
x 1.5
Rated
Amps
current
x 1.5
1.0
sec.
1.0
sec.
01
Rated
Amps
current
x 1.5
1.0
sec.
01

Advertisement

Table of Contents
loading

Table of Contents