Terminal Connector
Logic/Analog connector
Relay connector

Wire Connectors

Warning: Field wiring connections
must be made by a UL Listed and CSA
Certified ring lug terminal connector
sized for the wire gauge being used.
The connector must be fixed using the
crimping tool specified by the con-
nector manufacturer.

Fuse and Circuit Breaker Sizes

The inverter's input power wiring must include UL Listed, dual-element,
600V fuses, or UL Listed, inverse-time, 600V circuit breakers.
Motor output
kW
HP
0.2
1/4
0.4
1/2
0.55
3/4
0.75
1
1.1
1 1/2
1.5
2
2.2
3
3.7
5
5.5
7 1/2
7.5
10
Wire Size
Range
(AWG)
30—16
30—14
200V Models
Inverter Model
–002NFE(F)2/NFU2
–004NFE(F)2/NFU2
–005NFE(F)2
–007NFE(F)2/NFU2
–011NFE(F)2
–015NFE(F)2/NFU2
–022NFE(F)2/NFU2
–037LFU2
–055LFU2
–075LFU2
Torque Range
ft-lbs
0.16—0.19
0.37—0.44
Ampere Rating for
Fuse or Breaker
20 (single ph.)
15 (three ph.)
30 (single ph.)
20 (three ph.)
3
(N-m)
0.22—0.25
0.5—0.6
Terminal (ring lug)
Cable support
Cable
10
10
10
15
15
30
40
50