Prepare for Wiring

Step 5: It is very important to perform the wiring steps carefully and correctly. Before
5
proceeding, please study the caution and warning message herebelow.
WARNING: Use 60/75°C Cu wire only. (for models: WJ200-001L, -002L, -004L, -007L,
-015S, -022S, -004H, -007H, -015H, -022H and -030H)
WARNING: Use 75°C Cu wire only. (for models: WJ200-001S, -002S, -004S, -007S,
-015L, -022L, -037L, -055L, -075L, -110L, -150L, -040H, -055H, -075H,
-110H and -150H)
WARNING: "USE 60°C Cu wire only" or equivalent. For models WJ200-004H, -007H,
and –015H.
WARNING: "Open Type Equipment."
WARNING: "Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 240V maximum." For models with suffix S or L.
WARNING: "Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 480V maximum." For models with suffix H.
HIGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a danger of electric
shock and/or fire.
HIGH VOLTAGE: Wiring work shall be carried out only by qualified personnel.
Otherwise, there is a danger of electric shock and/or fire.
HIGH VOLTAGE: Implement wiring after checking that the power supply is OFF.
Otherwise, you may incur electric shock and/or fire.
HIGH VOLTAGE: Do not connect wiring to an inverter or operate an inverter that is
not mounted according to the instructions given in this manual. Otherwise, there is a
danger of electric shock and/or injury to personnel.
2−15