2–14
Step-by-Step Basic Installation
Determining Wire
and Fuse Sizes
Motor
Output
HP
kW
1/2
0.4
1
0.75
2
1.5
3
2.2
5
3.7
7.5
5.5
10
7.5
15
11
20
15
25
18.5
30
22
40
30
50
37
60
45
75
55
This section includes tables for 200V class and 400V class inverters (on the next page). The
following notes will help you read the tables in this section:
• Locate the row corresponding to the motor size and particular inverter in your application.
The maximum motor current determines the recommended wire sizes.
• The length column specifies that some inverters can optionally use a smaller wire gauge if
the wires are shorter than 10m and the inverter is located in an enclosure.
• Power Lines columns include wires connecting to terminals [R, S, T, U, V, W, P, PD, and N].
Only power input and motor leads will be fused: [R, S, T, U, V, and W]. The breaker ratings
(GFI—ground fault interrupter) are slightly higher than fuse ratings to allow for nominal
surges without tripping.
• The chassis ground columns list the Hitachi-recommended AWG and the minimal AWG for
UL conformity.
• The optional external braking resistor wiring only applies to a few models that have a built-
in braking unit. The other models use an optional external braking unit.
• Parallel wires increase effective wire gauge, and are denoted by "||" in the tables.
• Signal Lines, not listed in these tables, connect to the removable logic connector. The recom-
mended wire gauge for all wiring to the logic connector is 28 AWG (0.75 mm
use shielded wire for any analog signals.
200V
Inverter
Models
AWG
SJ300–004LFU
20
SJ300–007LFU
18
SJ300–015LFU
14
SJ300–022LFU
14
SJ300–037LFU
10
SJ300–055LFU
8
SJ300–075LFU
6
SJ300–110LFU
4
SJ300–150LFU
2
SJ300–185LFU
1
SJ300–220LFU
1/0
SJ300–300LFU
1/0 || 1/0
SJ300–370LFU
1/0 || 1/0
SJ300–450LFU
1/0 || 1/0
SJ300–550LFU
2/0 || 2/0
* See notes for wiring tables on the following page.
Wiring *1
Power Lines *3
Fuse
(UL-
Breaker
2
rated,
(GFI
mm
class J,
type) *2
600V)
1.25
10A
10A
1.25
10A
10A
2
10A
10A
2
15A
15A
3.5
20A
20A
5.5
30A
30A
8
40A
40A
14
60A
60A
22
80A
80A
14 || 14
100A
100A
14 || 14
125A
125A
22 || 22
150A
150A
30 || 30
175A
175A
38 || 38
225A
225A
60 || 60
250A
250A
2
). Be sure to
Brake Res.
Chassis Ground
AWG,
AWG,
2
AWG
mm
rec.
UL
16
14
1.25
20
16
14
1.25
18
16
14
1.25
14
16
14
1.25
14
10
12
3.5
10
8
10
5.5
8
8
10
8
8
4
10
14
8
3
8
22
3
8
22
2
8
30
2
6
30
1/0
6
38
3/0
6
38
3/0
4
60
2
mm
1.25
1.25
2
2
3.5
5.5
5.5