3−34
PID deviation output – If PID deviation "ε" exceeds the value in C044, output signal
configured as 04 (OD) is activated.
PID feedback comparison output – If PID feedback is out of the range between C052
and C053 output signal configured as 31 (FBV) is activated.
FW input
FBV output
PID scaling – When PID scale parameter (A075) is set, following variables are scaled.
(monitored) = (variable) ×(A075)
d004
A023
A031
PID Sleep Function
The inverter shuts off the output when the PID output becomes less than the specified
value (A156) in case of PID is set enabled, or shuts off when the frequency command
becomes less than the specified value in case of PID is set disabled. And if the PID
output or frequency command exceeds the specified value (A156) for a specified period
(A157), inverter automatically restarts the operation. This is the PID sleep function.
PID output
PID sleep function
triggering level
Run command (internal)
Run command (external)
PID Sleep function is always enabled, even the PID function is disabled.
PID feedback
ON
ON
F001
A011
A024
A025
A032
A033
A156
A157
PID sleep function action delay time
Run
ON
A012
A020
A026
A027
A034
A035
Stop
Run
C052
PID FBV output high limit
C053
PID FBV output low limit
Time
A220
A021
A028
A029
A101
A102
A156
Run
A022
A030
A145