The [AM] signal offset and gain are adjustable, as indicated below.
Func.
[AM] output gain
C106
[AM] output offset
C109
The graph below shows the effect of the gain and offset setting. To calibrate the [AM]
output for your application (analog meter), follow the steps below:
1. Run the motor at the full scale speed, or most common operating speed.
a. If the analog meter represents output frequency, adjust offset (C109) first, and
then use
b. If [AM] represents motor current, adjust offset (C109) first, and then use
to set the voltage for full scale output. Remember to leave room at the upper end
of the range for increased current when the motor is under heavier loads.
AM output offset adjustment
AM output
10V
C109=0~10
5V
0
NOTE: As mentioned above, first adjust the offset, and then adjust the gain. Otherwise
the required performance cannot be obtained because of the parallel movement of the
offset adjustment.
Description
to set the voltage for full scale output.
C106
Parallel
movement
Full scale (FS)
1/2 FS
Hz or A
Range
Default
0.~255.
100.
0.0~10.0
0.0
AM output gain adjustment
AM output
10V
5V
0
1/2 FS
4−91
BC106
C106=0~255
Full scale (FS)
Hz or A

Advertisement