Modbus Data Listing; Modbus Coil List - Hitachi WJ200 Series Instruction Manual

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

B−24

ModBus Data Listing

ModBus Coil List

The following tables list the primary coils for the inverter interface to the network. The
table legend is given below.
• Coil Number - The network
single bit (binary) value.
• Name - The functional name of the coil
• R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data
• Description - The meaning of each of the states of the coils
Coil
No.
0000h
unused
0001h
Operation command
0002h
Rotation direction command
0003h
External trip (EXT)
0004h
Trip reset (RS)
0005h
(Reserved)
0006h
(Reserved)
0007h
Intelligent input terminal [1]
0008h
Intelligent input terminal [2]
0009h
Intelligent input terminal [3]
000Ah
Intelligent input terminal [4]
000Bh
Intelligent input terminal [5]
000Ch
Intelligent input terminal [6]
000Dh
Intelligent input terminal [7]
000Eh
(Reserved)
000Fh
Operation status
0010h
Rotation direction
0011h
Inverter ready
0012h
(Reserved)
0013h
RUN (running)
0014h
FA1 (constant-speed reached)
0015h
FA2 (set frequency overreached)
0016h
OL (overload advance notice (1))
OD (output deviation for PID
0017h
control)
0018h
AL (alarm signal)
0019h
FA3 (set frequency reached)
001Ah
OTQ (over-torque)
001Bh
(Reserved)
001Ch
UV (undervoltage)
001Dh
TRQ (torque limited)
001Eh
RNT (operation time over)
001Fh
ONT (plug-in time over)
0020h
THM (thermal alarm signal)
0021h
(Reserved)
0022h
(Reserved)
0023h
(Reserved)
0024h
(Reserved)
0025h
(Reserved)
0026h
BRK (brake release)
0027h
BER (brake error)
0028h
ZS (0 Hz detection signal)
0029h
DSE (speed deviation maximum)
002Ah
POK (positioning completed)
002Bh
FA4 (set frequency overreached 2)
002Ch
FA5 (set frequency reached 2)
register address offset
Item
R/W
-
R/W
R/W
R/W
R/W
-
-
R/W
R/W
R/W
R/W
R/W
R/W
R/W
-
R
R
R
-
R
R
R
R
R
R
R
R
-
R
R
R
R
R
-
-
-
-
-
R
R
R
R
R
R
R
for the coil. The coil data is a
(Inaccessible)
1: Run, 0: Stop (valid when A002 = 03)
1: Reverse rotation, 0: Forward rotation (valid when A002 = 03)
1: Trip
1: Reset
-
-
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
-
1: Run, 0: Stop (interlocked to "d003")
1: Reverse rotation, 0: Forward rotation (interlocked to "d003")
1: Ready, 0: Not ready
-
1: Tripping, 0: Normal
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
-
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
-
-
-
-
-
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
Setting

Advertisement

Table of Contents
loading

Table of Contents