Off-Line Auto-Tuning Procedure (With Motor Rotation) - Hitachi WJ200 Series Instruction Manual

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

3−110

Off-line auto-tuning procedure (with motor rotation)

Step 1: Set motor size and
motor poles
H003
Motor size
H004
Motor poles
Result is displayed.
___o
Completed
___9
Failed
Step 5: Clear display by
STOP key
STOP
Step 6: Activate motor
constants by H002
H002
(Note 2) After auto-tuning is completed, be sure to set 01 in H002/H202, otherwise measured data is
not effective.
(Note 3) Speed "X" of above (5) depends on accel/deceleration time. (T: Larger time of accel or
deceleration time)
0 < T < 50 [s] :
50 ≤ T < 100 [s] :
100 ≤ T [s] :
(Note 4) If auto-tuning is failed, try to execute again.
(Note 5) If the inverter trips during the auto-tuning, the auto-tuning is interrupted. After removing
the cause of trip, retry auto-tuning from the beginning.
(Note 6) If inverter is stopped during auto-tuning by stop command (by STOP key or deactivate RUN
input), measured constants could remain. Be sure to execute auto-tuning again.
(Note 7) If auto-tuning is attempted in free V/f setting, auto-tuning will fail with error display.
Step 2: Set base freq. and
AVR voltage
A003
A082
Auto-tuning starts.
When RUN cmd. is given, the motor runs according to
following steps.
(1) 1st AC excitation (no rotation)
(2) 2nd AC excitation (no rotation)
(3) 1st DC excitation (no rotation )
(4) V/f operation (80% of base freq.)
(5) SLV operation (X % of base freq.)
02
(6) 2nd DC excitation (no rotation)
SET
(Note 1): When no-rotation setting (H001=01), (4) and (5) are skipped.
X=40%
X=20%
Base freq.
AVR voltage
X=10%
Step 3: Enable auto-tuning
H001
02
SET
Step 4: Start the inverter
according to RUN cmd.
source
RUN
(Note 1)