User Parameter Registration; Automatic User Parameter Registration - Hitachi WJ200 Series Instruction Manual

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

User Parameter Registration

Parameter group "U" is the user parameter. Any function code can be chosen to registor
on this parameter up to 32. When display mode is set to be "user parameter" (b037= 02)
then is U001 to U032 and d001, F001, b037 are displayed.
Func.
Name
Code
Function code display
b037
restriction
User parameters 1 to 32
u001
~
u032

Automatic User Parameter Registration

The automatic user parameter setting function allows you to make the inverter
automatically record changed function codes in U001 to U032. You can use the stored
function codes as a history of data change. To enable this function, select "01" (enabling
automatic user parameter setting) for the b039.
When any data is changed and SET key is pressed, the function code will be stored in
U001 to U032 sequentially.
The latest data is in U001, and the oldest one is in U032.
Stored function codes in U001 to U032 are not duplicated. If duplicated function code is
changed, old existing function code is deleted. If number of changed function code
exceeds 32, the oldest one in U032 is deleted.
Func.
Name
Code
Automatic user parameter
B039
registration
User parameters 1 to 32
u001
~
u032
"b" Function
Description
Seven option codes:
00...Full display
01...Function-specific display
02...User setting (and b037)
03...Data comparison display
04...Basic display
05...Monitor display only
Set range,
no"
d001~p183
"
,
"b" Function
Description
Two option codes:
00...Disable
01...Enable
Set range,
no"
d001~p183
"
,
3−61
Run
Defaults
Mode
Lnitial data
Units
Edit
04
Defaults
Run
Mode
Lnitial data
Units
Edit
00

Advertisement

Table of Contents
loading