Selecting Functions and Editing Parameters

To prepare to run the motor in the powerup test, this section will show how to
configure the necessary parameters:
1. Select the digital operator as the source of motor speed command (A001=02).
2. Select the digital operator as the source of the RUN command (A002=02).
3. Set the motor base frequency (A003) and AVR voltage of the motor (A082).
4. Set the motor current for proper thermal protection (b012).
5. Set the number of poles for the motor (H004).
The following series of programming tables are designed for successive use. Each table
uses the previous table's final state as the starting point. Therefore, start with the first
and continue programming until the last one. If you get lost or concerned that some of
the other parameters setting may be incorrect, refer to "Restoring Factory Default
Settings" on page 6-8.
Prepare to Edit Parameters – This sequence begins with powering ON the inverter,
then it shows how to navigate to the "A" Group parameters for subsequent settings.
You can also refer to the "Keypad Navigation Map" on page 2-26 for orientation
throughout the steps.
Turn ON the inverter
Press the ESC key.
Press the ESC key 2 times.
1. Select the digital operator for Speed Command – The inverter output frequency
can be set from several sources, including an analog input, memory setting, or the
network, for example. The powerup test uses the keypad as the speed control source
for your convenience. Note that the default setting depends on the country.
(Starting point)
Press the SET key
Press the
Press the SET key to store
Action
Action
key to select
/
Display
Func./Parameter
Inverter output frequency displayed
0
0
.
(0Hz in stop mode)
d001
"d" group selected
A001
"A" group selected
Display
Func./Parameter
"A" Group selected
A001
Speed command source setting
00...Potentiometer of ext. operator
01...Control terminals
01
02...Digital operator (F001)
03...ModBus network
etc.
02
02...Digital operator (selected)
A001
Stores parameter, returns to "A001"
2−29