Determining Wire And Fuse Sizes - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

2–14
Step-by-Step Basic Installation
Determining Wire
and Fuse Sizes
Motor
Output
HP
kW
2
1.5
3
2.2
5
3.7
7.5
5.5
10
7.5
15
11
20
15
25
18.5
30
22
40
30
50
37
60
45
75
55
100
75
This section includes tables for 200V class and 400V class inverters (on the next page). The
following notes will help you read the tables in this section:
• Locate the row corresponding to the motor size and particular inverter in your application.
The maximum motor current determines the recommended wire sizes.
• The length column specifies that some inverters can optionally use a smaller wire gauge if
the wires are shorter than 10m and the inverter is located in an enclosure.
• Power Lines columns include wires connecting to terminals [R, S, T, U, V, W, P, PD, and N].
Only power input and motor leads will be fused: [R, S, T, U, V, and W]. The breaker ratings
(GFI—ground fault interrupter) are slightly higher than fuse ratings to allow for nominal
surges without tripping.
• The chassis ground columns list the Hitachi-recommended AWG and the minimal AWG for
UL conformity.
• The optional external braking resistor wiring only applies to a few models that have a built-
in braking unit. The other models use an optional external braking unit.
• Parallel wires increase effective wire gauge, and are denoted by "||" in the tables.
• Signal Lines, not listed in these tables, connect to the removable logic connector. The recom-
mended wire gauge for all wiring to the logic connector is 28 AWG (0.75 mm
use shielded wire for any analog signals.
200V
Inverter
Models,
AWG
L300P
*3
–015LFU2
14
–022LFU2
14
–037LFU2
10
–055LFU2
8
–075LFU2
6
–110LFU2
4
–150LFU2
2
–185LFU2
1
–220LFU2
1/0
–300LFU2
1/0
–370LFU2
1/0 || 1/0
–450LFU2
1/0 || 1/0
–550LFU2
2/0 || 2/0
–750LFU2
3/0 || 3/0
Wiring *1
Power Lines *3
Fuse
(UL-
Breaker
2
mm
rated,
( GFI
*3
class J,
type) *2
600V)
2
10A
15A
2
15A
20A
3.5
20A
30A
5.5
30A
50A
8
40A
60A
14
60A
75A
22
70A
100A
14 || 2
90A
100A
38
100A
150A
22 || 22
150A
200A
30 || 30
175A
225A
38 || 38
200A
225A
60 || 60
250A
350A
80 || 80
300A
350A
2
). Be sure to
Brake Res.
Chassis Ground
AWG,
AWG,
2
AWG
mm
rec.
UL
16
14
1.25
14
16
14
1.25
14
10
12
3.5
10
8
10
5.5
8
8
10
8
8
4
10
14
8
3
8
22
8
3
8
22
2
8
30
2
6
30
1/0
6
50
3/0
6
80
3/0
4
80
3/0
4
80
2
mm
2
2
3.5
5.5
5.5
5.5
5.5