B−50
(vi) List of registers (2nd control settings)
Register
Function name
No.
2103h
Acceleration time (1),
2nd motor
2104h
2105h
Deceleration time (1),
2nd motor
2106h
2107h to
unused
2200h
(vii) List of registers (function modes for the 2nd control settings)
Register
No.
2201h
Frequency source, 2nd motor
2202h
Frequency source, 2nd motor
2203h
Base frequency, 2nd motor
Maximum frequency,
2204h
2nd motor
2205h to
(Reserved)
2215h
2216h
Multispeed frequency setting,
2nd motor
2217h
2218h to
(Reserved)
223Ah
Torque boost method
223Bh
selection, 2nd motor
Manual torque boost value,
223Ch
2nd motor
Manual torque boost
223Dh
frequency, 2nd motor
V/F characteristic curve
223Eh
selection, 2nd motor
223Fh
V/f gain, 2nd motor
Voltage compensation gain
2240h
setting for automatic torque
boost, 2nd motor
Slippage compensation gain
2241h
setting for automatic torque
boost, 2nd motor
2242h to
(Reserved)
224Eh
224Fh
Frequency upper limit,
2nd motor
2250h
2251h
Frequency lower limit,
2nd motor
2252h
2253h to
(Reserved)
2268h
2269h
AVR function select, 2nd motor
226Ah
AVR voltage select, 2nd motor
226Bh to
(Reserved)
226Eh
Function code
F202 (high)
F202 (low)
F203 (high)
F203 (low)
Function name
A220 (high)
A220 (low)
A261 (high)
A261 (low)
A262 (high)
A262 (low)
R/W
Monitoring and setting items
R/W
1 to 360000
R/W
R/W
1 to 360000
R/W
-
-
Inaccessible
Function
R/W
Monitoring and setting items
code
0 (keypad potentiometer), 1 (control
circuit terminal block), 2 (digital
A201
R/W
operator), 3 (Modbus), 4 (option ), 6
(pulse train input), 7 (easy sequence),
10 (operation function result)
1 (control circuit terminal block), 2
A202
R/W
(digital operator), 3 (Modbus), 4
(option)
300 to "maximum frequency, 2nd
A203
R/W
motor"
A204
R/W
300 to 4000
-
-
Inaccessible
R/W
0 or "start frequency" to "maximum
frequency, 2nd motor"
R/W
-
-
Inaccessible
0 (manual torque boost), 1 (automatic
A241
R/W
torque boost)
A242
R/W
20 to 200
A243
R/W
0 to 255
0 (VC), 1 (VP), 2 (free V/f), 3
A244
R/W
(sensorless vector control)
A245
R/W
20 to 100
A246
R/W
0 to 255
A247
R/W
0 to 255
-
-
Inaccessible
R/W
00 or "2nd minimum frequency limit"
to "maximum frequency, 2nd motor"
R/W
R/W
00 or "start frequency" to "maximum
frequency, 2nd motor limit"
R/W
-
-
Inaccessible
0 (always on), 1 (always off), 2 (off
A281
R/W
during deceleration)
200 V class: 0 (200)/1 (215)/2 (220)/3
(230)/4 (240)
A282
R/W
400 V class: 5 (380)/6 (400)/7 (415)/8
(440)/9 (460)/ 10 (480)
-
-
Inaccessible
Data
resolution
0.01 [sec.]
0.01 [sec.]
-
Data
resolution
-
-
0.1 [Hz]
0.1 [Hz]
-
0.01 [Hz]
-
-
1 [%]
1 [%]
-
1 [%]
1
1
-
0.01 [Hz]
0.01 [Hz]
-
-
-