5. Set the Number of Motor Poles – The motor's internal winding arrangement
determines its number of magnetic poles. The specification label on the motor usually
indicates the number of poles. For proper operation, verify the parameter setting
matches the motor poles. Many industrial motors have four poles, corresponding to the
default setting in the inverter (H004).
Follow the steps in the table below to verify the motor poles setting and change if
necessary (the table resumes action from the end of the previous table.)
Action
(Starting point)
Press the ESC key two times
Press the
key three times
Press the SET key.
Press the
/
Press the SET key.
This step concludes the parameter setups for the inverter. You are almost ready to run
the motor for the first time!
TIP: If you became lost during any of these steps, first observe the state of the PRG
LED. Then study the "Keypad Navigation Map on page 2-26 to determine the current
state of the keypad controls and display. As long as you do not press the SET key, no
parameter will be changed by keypad entry errors. Note that power cycling the inverter
causes it to power up Monitor Mode, displaying the value for D001 (output frequency).
The next section will show you how to monitor a particular parameter from the display.
Then you will be ready to run the motor.
Display
b012
H001
H004
H004
H004
key to select
H004
Func./Parameter
Level of electronic thermal setting
"H" Group selected
Motor poles parameter
2 = 2 poles
4 = 4 poles (default)
6 = 6 poles
8 = 8 poles
10 = 10 poles
Set to your motor specs (your display
may be different)
Store parameter, returns to "H004"