3−65
NOTE: If the DC bus voltage comes down to the UV level during this operation, the
inverter trips with under-voltage and motor will free-run (coast) to a stop.
NOTE: If the set value of B052<B051, then the inverter internally swaps the B052 and
B051 values. However the displayed values are not changed.
NOTE: This function cannot be interrupted until it is completed. So if the power is
restored during this operation, wait until the operation is done (motor stops) and then
give the run command.