Hitachi WJ200 Series Instruction Manual page 6

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Wiring – Warnings for Electrical Practice and Wire Specifications
WARNING: "USE 60/75°C Cu wire only" or equivalent. For models WJ200-001L, -002L,
-004L, -007L, -015S, -022S, -004H, -007H, -015H, -022H and -030H.
WARNING: "USE 75°C Cu wire only" or equivalent. For models WJ200-001S, -002S,
-004S, -007S, -015L, -022L, -037L, -055L, -075L, -110L, -150L, -037H, -040H, -055H,
-075H, -110H and -150H.
WARNING: "Open Type Equipment."
WARNING: "Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 240V maximum when protected by Class CC, G, J or R fuses or
circuit breaker having an interrupting rating not les than 100,000 rms symmetrical
amperes, 240 volts maximum". For models with suffix S, N or L.
WARNING: "Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 480V maximum when protected by Class CC, G, J or R fuses or
circuit breaker having an interrupting rating not les than 100,000 rms symmetrical
amperes, 480 volts maximum." For models with suffix H.
HIGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a danger of electric
shock and/or fire.
HIGH VOLTAGE: Wiring work shall be carried out only by qualified personnel.
Otherwise, there is a danger of electric shock and/or fire.
HIGH VOLTAGE: Implement wiring after checking that the power supply is OFF.
Otherwise, you may incur electric shock and/or fire.
HIGH VOLTAGE: Do not connect wiring to an inverter operate an inverter that is not
mounted according to the instructions given in this manual.
Otherwise, there is a danger of electric shock and/or injury to personnel.
WARNING: Make sure the input power to the inverter is OFF. If the drive has been
powered, leave it OFF for five minutes before continuing.
CAUTION: Power terminal assignment is different compared to old models such as
L100, L200 series, etc,. Pay attention when wiring the power cable.
v
...2-18
...2-18
...2-18
...2-18
...2-18
...2-18
...2-18
...2-23
...2-11
~21

Advertisement

Table of Contents
loading

Table of Contents