Wire Connectors; Fuse And Circuit Breaker Sizes - Hitachi SJ300 Series Quick Reference Manual

Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

Motor output
kW
HP
132
175
150
200

Wire Connectors

Warning: Field wiring connections
must be made by a UL Listed and CSA
Certified ring lug terminal connector
sized for the wire gauge being used.
The connector must be fixed using the
crimping tool specified by the con-
nector manufacturer.

Fuse and Circuit Breaker Sizes

The inverter's input power wiring must include UL Listed, dual-element,
600V fuses, or UL Listed, inverse-time, 600V circuit breakers.
Motor output
kW
HP
0.4
1/2
0.75
1
1.5
2
2.2
3
3.7
5
5.5
7 1/2
7.5
10
11
15
15
20
18.5
25
22
30
400V Models
Inverter
Model
–1320HFU/E
–1500HFU/E
200V Models
Inverter
Model
–004LFU
–007LFU
–015LFU
–022LFU
–037LFU
–055LFU
–075LFU
–110LFU
–150LFU
–185LFU
–220LFU
Wire Size (AWG)
3/0 || 3/0
3/0 || 3/0
Ampere Rating for
Fuse or Breaker
10
10
10
15
20
30
40
60
80
100
125
3
Torque
ft-lbs
10.1
10.1
Terminal (ring lug)
Cable support
Cable
(N-m)
13.7
13.7