Input Range Settings – The parameters in the following table adjust the input
characteristics of the VR (POT meter on external operator) input. When using the
inputs to command the inverter output frequency, these parameters adjust the starting
and ending ranges for the current, as well as the output frequency range. Related
characteristic diagrams are located in " Analog Input Settings " in this chapter.
Analog sampling setting is the value specified in A016.
Func.
Name
Code
[VR] input active range start
A161
frequency
[VR] input active range end
A162
frequency
[VR] input active range
A163
start %
[VR] input active range end %
A164
[VR] input start frequency
A165
select
Refer to parameter A011 to A015 for analog voltage input.
"A" Function
Description
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
The starting point (offset) for
the current input range,
range is 0. to 100.%
The ending point (offset) for
the current input range,
range is 0. to 100.%
Two options; select codes:
00...Use offset (A161 value)
01...Use 0Hz
Defaults
Run
Mode
Lnitial data
Units
Edit
0.00
Hz
0.00
Hz
0.
%
100.
%
01
3−43