The output logic conversion is programmable for terminal [11], [12] and the alarm relay
terminal. The open-collector output terminal [11] and [12] defaults to normally open (active
low), but you can select normally closed (active high) for the terminal in order to invert the
sense of the logic. You can invert the logical sense of the alarm relay output as well.
Func.
Code
Output [11] active state
C031
Output [12] active state
C032
Alarm relay active state
C036
You can also adjust the output with ON/OFF delays.
Func.
Code
Output [11] on delay
C130
Output [11] off delay
C131
Output [12] on delay
C132
Output [12] off delay
C133
Relay output on delay
C140
Relay output off delay
C141
NOTE: If you are using the output terminal OFF delay feature (any of C145, C149 > 0.0
sec.), the [RS] (reset) terminal affects the ON-to-OFF transition slightly. Normally (with
using OFF delays), the [RS] input causes the motor output and the logic outputs to turn
OFF together, immediately. However, when any output uses an OFF delay, then after
the [RS] input turns ON, that output will remain ON for an additional 1 sec. period
(approximate) before turning OFF.
"C" Function
Name
Select logic conversion, two option
codes:
00...normally open [NO]
01...normally closed [NC]
"C" Function
Name
Set range is 0.0 to 100.0 sec.
Description
Description
Run
Defaults
Mode
Lnitial data
Units
Edit
00
00
01
Defaults
Run
Mode
Lnitial data
Units
Edit
0.0
Sec.
0.0
Sec.
0.0
Sec.
0.0
Sec.
0.0
Sec.
0.0
Sec.