Write in Holding Registers [17h]:

This function is to read and write data in consecutive holding registers. An example
follows:
• Write "50.0Hz" as the set frequency (F001) in an inverter having a slave address "1"
and then to read out the output frequency (d001).
Query:
No.
Field Name
1
Slave address *1
2
Function code
3
Start address to read *3
(high order)
4
Start address to read *3
(low order)
5
Number of holding
registers to read (high
order)
6
Number of holding
registers to read (low
order)
7
Start address to write
*3
(high order)
8
Start address to write
*3
(low order)
9
Number of holding
registers to write (high
order)
10
Number of holding
registers to write (low
order)
11
Byte number to write*2
12
Change data 1
(high order)
13
Change data 1
(low order)
14
Change data 2
(high order)
15
Change data 2
(low order)
16
CRC-16 (high order)
17
CRC-16 (low order)
Note 1:
Register address value (transmitted on Modbus line) is 1 less than the
Register Number.
When writing in selected holding registers fails, see the exception response.
Response:
Example
No.
(Hex)
01
1
Slave address
17
2
Function code
10
3
Byte number n
00
4
Register Data 1 (high
order)
00
5
Register Data 1 (low
order)
02
6
Register Data 2 (high
order)
00
7
Register Data 2 (low
order)
00
8
CRC-16 (high order)
00
9
CRC-16 (low order)
02
04
00
00
13
88
F4
86
Example
Field Name
(Hex)
B−17
01
17
04
00
00
13
88
F4
71