Func.
Name
Code
Cooling fan control
B092
Clear elapsed time of
B093
cooling fan
Initialization target data
b094
Dynamic braking control
b095
(BRD) selection
BRD activation level
b096
Initialization trigger
b180
(*)
(*) Note: When 01 is set on b180, and SET key is pressed, initialization starts
immediately and there is not any way to restore the previous parameter setting. WJ200
doesn't have a method to trigger the initialization by key action as the other Hitachi
inverter models have.
"b" Function
Description
Selects when the fan is ON during
inverter operation, four options:
00...Fan is always ON
01...Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF)
02...Fan is temperature controlled
Two option codes:
00...Count
01...Clear
Select initialized parameters, four
option codes:
00...All parameters
01...All parameters except
in/output terminals and
communication.
02...Only registered parameters in
Uxxx.
03...All parameters except
registered parameters in Uxxx
and b037.
Three option codes:
00...Disable
01...Enable during run only
02...Enable always
Range is:
330 to 380V (200V class)
660 to 760V (400V class)
This is to perform initialization by
parameter input with b084, b085
and b094. Two option codes:
00...Initialization disable
01...Perform initialization
3−71
Run
Defaults
Mode
Lnitial data
Units
Edit
01
−
00
−
00
−
01
−
360/
V
720
00
−