No response occurs:

In the cases below, the inverter ignores a query and returns no response.
• When receiving a broadcasting query
• When detecting a transmission error in reception of a query
• When the slave address set in the query is not equal to the slave address of the
inverter
• When a time interval between data elements constituting a message is shorter than
3.5 characters
• When the data length of the query is invalid
• When broadcast message received.
NOTE: Provide a timer in the master and make the master retransmit the same query
when no response is made within a preset time period after the preceding query was
sent.