Free-run Stop

When the terminal [FRS] is turned ON, the inverter stops the output and the motor
enters the free-run state (coasting). If terminal [FRS] is turned OFF, the output
resumes sending power to the motor if the Run command is still active. The free-run
stop feature works with other parameters to provide flexibility in stopping and starting
motor rotation.
In the figure below, parameter
from 0 Hz (left graph) or the current motor rotation speed (right graph) when the [FRS]
terminal turns OFF. The application determines the best setting.
Parameter
B003
To disable this feature, use a zero delay time.
Motor speed
1
[FRS]
0
1
[FW,RV]
0
Option
Terminal
Code
Symbol
FRS
Free-run Stop
11
C001~C007
Valid for inputs:
B003, B088,
Required settings
Notes:
• When you want the [FRS] terminal to be active
low (normally closed logic), change the setting
(C011
to C017) that corresponds to the input
(C001
to C007) that is assigned the [FRS]
function.
B088
specifies a delay time before resuming operation from a free-run stop.
B088
=
00
Zero frequency start
Function Name
State
ON
OFF
to
C011
C017
selects whether the inverter resumes operation
Resume from motor speed
Motor speed
1
[FRS]
0
1
[FW,RV]
0
t
Description
Causes output to turn OFF, allowing motor to free
run (coast) to stop
Output operates normally, so controlled deceleration
and stops motor
Example (requires input configuration—
see
page
3–84):
7
6
5
4
See I/O specs on
page 4–6.
B088
=
01
Wait time
B003
t
FRS
3
2
1
L
PCS
P24
PLC
4−23