IGBT Test Method

The following procedure will check the inverter transistors (IGBTs) and diodes:
1. Disconnect input power to terminals [R, S, and T] and motor terminals [U, V, and
W].
2. Disconnect any wires from terminals [+] and [–] for regenerative braking.
3. Use a Digital Volt Meter (DVM) and set it for 1Ω resistance range. You can check the
status of the charging state of terminals [R, S, T, U, V, W, +, and –] of the inverter
and the probe of the DVM by measuring the charging state.
D1
D2
[R/L1]
[S/L2]
[T/L3]
D4
D5
Table Legend Almost infinite resistance: ≅ ∞ Ω Almost zero resistance: ≅ 0 Ω
Part
DVM
+
D1
[R] [+1]
[+1] [R]
D2
[S] [+1]
[+1] [S]
D3
[T] [+1]
[+1] [T]
D4
[R]
[–]
[–]
[R]
NOTE: The resistance values for the diodes or the transistors will not be exactly the
same, but they will be close. If you find a significance difference, a problem may exist.
NOTE: Before measuring the voltage between [+] and [–] with the DC current range,
confirm that the smoothing capacitor is discharged fully, then execute the tests.
[PD/+1] [P/+] [RB]
D3
+
D6
TR7
[N/ ]
-
Measured
Part
DVM
Value
≅ ∞ Ω
D5
[S] [–]
≅ 0 Ω
[–] [S]
≅ ∞ Ω
D6
[T] [–]
≅ 0 Ω
[–] [T]
≅ ∞ Ω
TR1 [U] [+]
≅ 0 Ω
[+] [U]
≅ 0 Ω
TR2
[V] [+]
≅ ∞ Ω
[+] [V]
TR3 [W] [+]
[+] [W]
TR1
TR2
TR4
TR5
Measured
Part
Value
+
≅ 0 Ω
TR4 [U] [–]
≅ ∞ Ω
[–] [U]
≅ 0 Ω
TR5 [V] [–]
≅ ∞ Ω
[–] [V]
≅ ∞ Ω
TR6 [W] [–]
≅ 0 Ω
[–] [W]
≅ ∞ Ω
TR7 [RB] [+]
≅ 0 Ω
[+] [RB]
≅ ∞ Ω
[RB] [–]
≅ 0 Ω
[–] [RB]
TR3
[U/T1]
[V/T2]
[W/T3]
TR6
DVM
Measured
Value
+
≅ 0 Ω
≅ ∞ Ω
≅ 0 Ω
≅ ∞ Ω
≅ 0 Ω
≅ ∞ Ω
≅ ∞ Ω
≅ 0 Ω
≅ ∞ Ω
≅ ∞ Ω
6−17