Hitachi WJ200 Series Instruction Manual page 147

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

3−66
Func.
Code
Controlled deceleration on
B050
power loss
DC bus voltage trigger
B051
level of ctrl. decel.
Over-voltage threshold of
B052
ctrl. decel.
Deceleration time of ctrl.
B053
decel.
Initial freq. drop of ctrl.
B054
decel.
"b" Function
Name
Four option codes:
00...Trips
01...Decelerates to a stop
02...Decelerates to a stop with DC
03...Decelerates to a stop with DC
Setting of DC bus voltage to start
controlled decel. operation. Range
is 0.0 to 1000.0
Setting the OV-LAD stop level of
controlled decel. operation. Range
is 0.0 to 1000.0
Range is 0.01 to 3600.0
Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
Description
bus voltage controlled
bus voltage controlled, then
restart
Run
Defaults
Mode
Lnitial data
Units
Edit
00
220.0/
V
440.0
360.0/
V
720.0
1.0
sec
0.0
Hz