3−70

Miscellaneous Settings

The miscellaneous settings include scaling factors, initialization modes, and others.
This section covers some of the most important settings you may need to configure.
Start frequency adjustment: B082 – When the inverter starts to run, the output
frequency does not ramp from 0Hz. Instead, it steps directly to the
(B082), and the ramp proceeds upward from there.
Initialization related: B084, B085, B094, B180 – These functions allow you to restore the
factory default settings. Please refer to "Restoring Factory Default Settings" in chapter
6.
Stop key enable function: B087 – This function allows you to decide whether the stop
key on the integrated operator is enabled or not.
Dynamic Braking related functions: B090, B095, B096, – These parameters are for using
the internal brake chopper so to get more regeneration torque of the motor.
Cooling Fan Control: B092 – You can select the performance of the cooling fan (if your
inverter model includes a fan). This function controls whether the cooling fan stops or
keeps on running after the inverter stops the motor. This can result in an additional
energy saving and extends fan life.
Func.
Code
Start frequency
B082
Initialization mode
B084
(parameters or trip
history)
Country for initialization
B085
STOP key enable
B087
Dynamic braking usage
b090
ratio
"b" Function
Name
Sets the starting frequency for the
inverter output, range is 0.10 to
9.99 Hz
Select initialized data, five option
codes:
00...Initialization disabled
01...Clears Trip history
02...Initializes all Parameters
03...Clears Trip history and
initializes all parameters
04...Clears Trip history and
initializes all parameters and
EzSQ program
Select default parameter values for
country on initialization, two
option codes:
00...area A
Select whether the STOP key on
the keypad is enabled, three option
codes:
00...Enabled
01...Disabled always
02... Disabled for stop
Selects the rate of use (in %) of the
regenerative braking resistor per
100 sec. intervals, range is 0.0 to
100%.
0%: Function disabled
>0%: Enabled, per value
Description
01...area B
start frequency
Run
Defaults
Mode
Lnitial data
Units
Edit
0.50
Hz
00
00
00
0.0
%