Accel/Decel - Hitachi WJ200 Series Instruction Manual

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

3−38

Accel/Decel

Standard acceleration and deceleration is
linear. The inverter CPU can also
calculate an S-curve acceleration or
deceleration curve as shown. This profile
is
useful
characteristics in particular applications.
Curve settings for acceleration and
deceleration are independently selected.
To enable the S-curve, use function A097
(acceleration) and A098 (deceleration).
Func.
Code
Acceleration curve selection
A097
Deceleration curve selection
A098
Acceleration curve constant
a131
Deceleration curve constant
a132
Curvature of EL-S-curve at
a150
the start of acceleration
Curvature of EL-S-curve at
a151
the end of acceleration
Curvature of EL-S-curve at
a152
the start of deceleration
Curvature of EL-S-curve at
a153
the end of deceleration
See next page for the details.
for
favoring
the
"A" Function
Name
Set the characteristic curve of
Acc1 and Acc2, five options:
00...linear
01...S-curve
02...U-curve
03...Inverse U-curve
04...EL S-curve
Set the characteristic curve of
Dec1 and Dec2, options are
same as above (a097)
Range is 01 to 10.
Range is 01 to 10.
Range is 0 to 50%
Range is 0 to 50%
Range is 0 to 50%
Range is 0 to 50%
Output
frequency
Accel. curve selection
Target
freq.
S-curve
load
A097
0
Acceleration period
Description
01
=
Linear
A097
00
=
Defaults
Run
Mode
Lnitial data
Edit
00
00
02
02
10.
10.
10.
10.
t
Units
%
%
%
%