Simple Positioning Setting - Hitachi WJ200 Series Instruction Manual

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

3−116

Simple positioning setting

- Set "03" in [EA] selection (P003), then pulse train input is used as feedback signal from encoder.
- Set "02" in simple positioning selection (P012), then simple positioning is enabled. (If "00" is set, "V/f
control with FB" is enabled. Please refer to xx for further information.
- Up to 8 position data are commanded by combination of 3 input terminals configured as CP1 to
CP3.
- Besides positioning input, RUN command (FW,RV) is necessary. Since rotation direction does not
matter for positioning, both FW and RV work as RUN command.
- Positioning speed depends on frequency source (A001).
- More than four digits are required for positioning data, but only four higher digits are displayed.
Code
P003
P004
P011
P012
P015
P026
P027
p072
p073
p075
P077
H050
H051
d029
d030
C102
C001
-C007
C021-C022
C026
(Note 1) If 7/EB terminal is used (P004=00~03), set 85 (EB) in input 7 (C007). ON is forward
Item
[EA] terminal selection
Feedback pulse train mode
Encoder PPR setting
Simple positioning selection
Creep speed
Over-speed error detection level
Speed deviation error level
Position range (Forward)
Position range (Reverse)
Positioning mode selection
Encoder disconnection timeout
Slip comp. P gain for FB V/f
Slip comp. I gain for FB V/f
Position setting monitor
Position feedback monitor
Reset selection
Input [1]~[7] function
Output [11][12] function
Alarm relay function
and OFF is reverse direction.
Data or data range
01
Encoder feedback
00
Single phase pulse train
01
90° ph. difference 2-ph. pulse train 1
02
90° ph. difference 2-ph. pulse train 2
03
Single phase pulse train + direction
32. to 1024.
02
Simple positioning enabled
Start freq. to .10.00Hz
0.0 to 150. %
0.00 to 120.0 Hz
Higher 4-digits displayed
0 to +268435455
Higher 4-digits displayed
–268435455 to 0
With limitation
00
No limitation (shorter route)
01
p004
0.0 to 10.0 s
0.0 to 10.00
0.0 to 1000. s
8435455 to +268435455
Internal data is not cleared by reset
03
PCLR: Pulse counter clear
47
EB: Rotation direction detection
85
DSE: Speed deviation excessive
22
POK: Positioning competion
23
Description
is to be set 00 or 01