Digital Operator Display Selection - YASKAWA GPD-506V Technical Manual

Table of Contents

Advertisement

5 . 8
D I G I T A L OPERATOR DISPLAY SELECTION
n 0 2 3 : Operator Display Mode
Reference and Indication
This parameter determines the scaling of the Digital Operator display, for both Output
Frequency and all Frequency References.
DATA
DATA
0*
(factory
setting)
1
2 t o 39
(no. of motor
poles)
4 0
t o
49 9 9
(Display Units)
DISPLAY
DISPLAY
Output frequency, in increments of 0.1 Hz.
Output frequency, in increments of 0.1 %.
Motor synchronous speed (P =
in increments of 1 RPM
(3999 max).
NOTE: If motor synchronous speed exceeds
3999 RPM, display holds at 3 9 9 9 .
Line speed or other parameter.
X X X X
(See CAUTION on next page)
EXAMPLE:
To display Line Speed, based on
54.3 FPM at 60 Hz:
n023 setting = " 15 4 3 "
5-9
Factory setting: 0
Range: 0 to 4999
120 x F
)
N
S
P = no. of motor poles
F = Frequency
N
= motor synchronous speed
S
Parameter value at maxi-
mum frequency (n 0 1 1 )
(include leading zeroes
if necessary)
Location of decimal point:
_ = _ X X X
1 = X X X. X
2 = X X. X X
3 = X. X X X
4 = X. X X O
( X X X *10)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-p5m

Table of Contents