Efficiency; Cooling - ABB DriveIT ACH550-01 User Manual

Hide thumbs Also See for DriveIT ACH550-01:
Table of Contents

Advertisement

ACH550 User's Manual
X1
10
+24V
11
GND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
1
Digital input impedance 1.5 kohm. Maximum voltage for digital
inputs is 30 V.
2
Default values depend on the macro used. Values specified are
for the default macro. See section "Wiring and applications".
Note! Terminals 3, 6, and 9 are at the same potential.
Appendix and available options
Hardware description
Auxiliary voltage output 24 VDC / 250 mA (reference to
GND). Short circuit protected.
Auxiliary voltage output common. (Connected internally
as floating.)
Digital input common. To activate a digital input, there
must be ≥+10 V
(or ≤-10 V) between that input and DCOM. The 24 V may
be provided by the ACH550 (X1-10) or by an external
12...24 V source of either polarity.
Digital input 1, programmable. Default
Digital input 2, programmable. Default
Digital input 3, programmable. Default
(code).
Digital input 4, programmable. Default
sel (code).
Digital input 5, programmable. Default
Digital input 6, programmable. Default
Relay output 1, programmable.
2
Default
Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)
Relay output 2, programmable.
2
Default
Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)
Relay output 3, programmable.
2
Default
Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)
2
= start/stop.
2
= not used.
2
= start enable sel
2
= constant speed
2
= not used..
2
= not used.
= Ready
= Running
= Fault (-1)