ABB DriveIT ACH550-01 User Manual page 387

Hide thumbs Also See for DriveIT ACH550-01:
Table of Contents

Advertisement

ACH550 User's Manual
Fuses
Branch circuit protection must be provided by the end-user,
sized per the NEC and local codes. Recommendations for fuses
for short-circuit protection on the mains cable are below.
Fuses, 380...480 volt drives
ACH550-
x1-
current
see below
-02A4-4
2.4
-03A3-4
3.3
-04A1-4
4.1
-05A4-4
5.4
-06A9-4
6.9
-08A8-4
8.8
-012A-4
11.9
-015A-4
15.4
-023A-4
23
-031A-4
31
-038A-4
38
-044A-4
44
-059A-4
59
-072A-4
72
-077A-4
77
-096A-4
96
-124A-4
124
-157A-4
157
-180A-4
180
*Example
Appendix and available options
Input
A IEC269 gG
A
10
16
25
35
50
63
80
125
160
200
250
Mains fuses
Bussmann
A UL class T
10
JJS-10
15
JJS-15
20
JJS-20
30
JJS-30
40
JJS-40
50
JJS-50
60
JJS-60
80
JJS-80
90
JJS-90
100
JJS-100
125
JJS-125
175
JJS-175
200
JJS-200
250
JJS-250
type*
383

Advertisement

Table of Contents
loading

This manual is also suitable for:

Driveit ach550-uh

Table of Contents