ACH550 User's Manual
Code
Description
4009
100 % VALUE
Defines (together with the previous
parameter) the scaling applied to the
PID controller's actual values.
• Units and scale are defined by parameters 4006 and 4007.
4010
SET POINT SEL
Defines the reference signal source for the PID controller.
• Parameter has no significance when the PID regulator is by-
passed (see 8121
0 = keypad – Control panel provides reference.
1 =
1 – Analog input 1 provides reference.
AI
2 =
2 – Analog input 2 provides reference.
AI
8 = comm – Fieldbus provides reference.
9 =
+
COMM
combination as the reference source. See Analog Input Reference
Correction below.
10 =
COMM
combination as the reference source. See Analog Input Reference
Correction below.
11 =
3
, 4
DI
U
control, provide reference.
3 increases the speed (the U stands for "up")
DI
4 decreases the reference (the D stands for "down").
DI
• Parameter 2205
rate of change.
• R = Stop command resets the reference to zero.
• NC = Reference value is not copied.
Parameter listing and descriptions
REG BYPASS CTRL
1 – Defines a fieldbus and analog input 1 (
AI
*
1 – Defines a fieldbus and analog input 1 (
AI
(
) – Digital inputs, acting as a motor potentiometer
D
RNC
ACCELER TIME
Range
Unit and scale
defined by par.
4006 and 4007
0...19
).
2 controls the reference signal's
1)
AI
1)
AI
273