ACH550 User's Manual
Code
Description
4024
PID SLEEP DELAY
Sets the time delay for the PID sleep function – a motor speed /
frequency below 4023
enables the PID sleep function (stopping the drive).
• See 4023
4025
WAKE-UP DEVIATION
Defines the wake-up deviation –
a deviation from the setpoint greater
than this value, for at least the time period 4026
starts the PID controller.
• Parameters 4006 and 4007 define the units and scale.
• Parameter 4005 = 0,
Wake-up level = Setpoint - Wake-up deviation.
• Parameter 4005 = 1,
Wake-up level = Setpoint + Wake-up deviation.
• Wake-up level can be above or below setpoint.
See figures:
• C = Wake-up level when parameter 4005 = 1
• D = Wake-up level when parameter 4005 = 0
• E = Feedback is above wake-up level and lasts longer than 4026
-
WAKE
UP DELAY
• F = Feedback is below wake-up level and lasts longer than 4026
-
WAKE
UP DELAY
025
etpoint
025
4026
WAKE-UP DELAY
Defines the wake-up delay –
a deviation from the setpoint greater than 4025
for at least this time period, re-starts the PID controller.
• See 4023
Parameter listing and descriptions
PID SLEEP LEVEL
above.
PID SLEEP LEVEL
– PID function wakes up.
– PID function wakes up.
E
P 4026
P 4026
F
above.
PID SLEEP LEVEL
Range
0.0...3600 s
for at least this time period
Unit and scale
defined by par.
4106 and 4107
-
WAKE
C
D
t
0...60s
-
WAKE
UP DEVIATION
, re-
UP DELAY
,
281